The Allen-Bradley 1762-IR4 provides precise temperature and resistance measurement for industrial applications. This module connects seamlessly to MicroLogix controllers. It reads data from four independent input channels. Each channel supports various RTD and resistance signals. This design delivers reliable performance in demanding environments.
Expert Technical Evaluation & Performance Analysis
The 1762-IR4 uses a Delta-Sigma converter for high-accuracy analog-to-digital conversion. This method provides excellent noise rejection. You can select from six input filters including 10 Hz, 50 Hz, 60 Hz, 250 Hz, 500 Hz, and 1 kHz. The fastest update occurs with one channel using the 1 kHz filter. The slowest update happens with all six channels using the 10 Hz filter. Autocalibration and lead wire compensation cycles increase the update time.
This module supports a wide sensor range. It works with 100, 200, 500, and 1000 Ohm Platinum 385 and 3916 RTDs. It also handles 10 Ohm Copper, 120 Ohm Nickel, and 604 Ohm Nickel-Iron sensors. The module accepts 2-wire, 3-wire, and 4-wire RTD configurations. For resistance devices, it reads 0 to 150, 0 to 500, 0 to 1000, and 0 to 3000 Ohm ranges. This flexibility makes it ideal for temperature and displacement monitoring.

The module dissipates only 1.5 Watts of heat. Its compact size measures 90 x 87 x 40 mm. You can mount it on a DIN rail or a panel. The module installs in non-hazardous, dry, and clean areas. Keep it away from electrical noise and heat sources. The single diagnostic LED shows status and power information. This feature helps identify problems quickly.
Step-by-Step Configuration & Installation Guide
Configure the module after installation. The module uses six input words and five configuration words. Set operation details for each channel separately. The module auto-calibrates when you enable a channel. You can also program it to calibrate every five minutes. This ensures ongoing measurement accuracy.

For wiring, connect your RTD or resistance device to the terminal block. Use the correct wiring type for your sensor configuration. The finger-safe cover protects the wiring area. Always wire safety circuits in series to the master relay. When troubleshooting, stand away from the equipment. Always check for program changes before you work on the system.
The 1762-IR4 performs both module and channel diagnostics. This feature helps isolate faults quickly. You can access data in raw/proportional format. Other options include engineering units x1, engineering units x10, scaled-for-PID, and percent full scale. This variety of formats suits different control strategies.
Logistics & Standard Packaging Details

We offer express shipping through FedEx, UPS, and DHL. This ensures fast and reliable delivery for your critical automation projects.