Precision Temperature Measurement in Industrial Automation
In process industries, accurate temperature monitoring is critical for product quality and safety. Thermocouple-based systems are widely used due to their wide range and ruggedness. The Schneider 140ATI03000 analog input module addresses these needs with eight dedicated thermocouple channels and high-resolution measurement.
Introducing the 140ATI03000
Part of the Modicon Quantum automation platform, the 140ATI03000 is an analog input module designed for thermocouple sensors. It supports multiple thermocouple types including J, E, K, T, R, and S, covering temperature ranges from -270 °C to 1665 °C depending on the type. This flexibility makes it suitable for diverse applications from cryogenic to high-temperature processes.
Key Technical Specifications
The module provides 8 analog inputs with 16-bit resolution, ensuring fine granularity in temperature readings. It incorporates a notch filter at 50/60 Hz and a single-pole low-pass filter at 20 Hz to reject electrical noise. Absolute accuracy error is ±2 °C plus 0.1% of reading for types J, E, K, and T, and ±4 °C plus 0.1% for types R and S. Linearity error is maintained at 1 °C or 0.1 °C across all ranges.
Isolation is a key feature: channel-to-bus isolation is rated at 1780 V AC for 60 seconds and 2500 V DC for 60 seconds, while channel-to-channel isolation is 300 V DC and 220 V AC. Common mode rejection exceeds -120 dB at 50/60 Hz, enhancing signal integrity in noisy industrial environments.

Application Scenarios for the 140ATI03000
In a chemical processing plant, the module can monitor reactor temperatures using type K thermocouples, ensuring reactions stay within safe limits. For a food processing facility, type T thermocouples provide accurate readings for freezing tunnels. The module's cold junction compensation (internal, 0–60 °C) simplifies installation by eliminating external compensation hardware.
Compatibility and Integration
The 140ATI03000 integrates seamlessly into the Modicon Quantum automation platform. It requires 10 input words of addressing and draws 280 mA from the bus. The module includes diagnostic LEDs: one green for bus communication, one red for external fault, and eight green/red LEDs per channel for status and fault indication. This aids quick troubleshooting on the plant floor.
Market Impact and Business Value
By providing reliable, high-resolution temperature measurement, the 140ATI03000 helps reduce process variability and improve yield. Its robust isolation protects sensitive control systems, minimizing downtime. With a power dissipation of only 1.5 W, it contributes to energy-efficient panel designs.

Frequently Asked Questions About the 140ATI03000
What thermocouple types does the 140ATI03000 support?
The module supports types J, E, K, T, R, and S, with temperature ranges from -270 °C to 1665 °C depending on the type. For example, type K covers -270 to 1370 °C, while type R covers 50 to 1665 °C.
What is the update time of the module?
The update time is 1000 ms, providing stable readings suitable for most process control loops. This ensures the control system receives consistent temperature data.
Does the module include fault detection?
Yes, the 140ATI03000 detects broken wire and overtracking scale faults. It also provides LED indicators for channel status and external faults, enabling rapid identification of issues.
Company Strength and Supply Assurance
Petro Auto Tech offers the Schneider 140ATI03000 with expert support for integration and selection. Please verify current lifecycle status and availability with Petro Auto Tech before ordering to ensure timely delivery for your project.